3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Pool free chlorine disinfectant residual was below 1 ppm. Free chlorine tested at 0.4 ppm at the time of inspection. The pool is closed until free chlorine is above 1.0 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. Correct By: 01-Dec-2023
3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Disinfection residuals were not tested daily at pool side and/or at the required intervals for pools/automatic chemical controllers/special features. Pool chemistry was not tested for November 16, 17, 29 or 30.
Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. If an ACC is in use the disinfectant residual must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the disinfectant residual must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use. Correct By: 01-Dec-2023
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Combined chlorine was not tested daily at pool side prior to use. No pool chemistry records for November 16, 17, 29 or 30.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use. Correct By: 01-Dec-2023
3701-31-04 (B)(4)(a)(iii) / pH is tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Repeat pH was not tested daily at pool side and/or at required intervals for pools/automatic chemical controllers/special features. No pH records for November 16, 17, 29 or 30.
pH must be tested prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use pH must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the pH must be tested at 1 special feature every 6 hours the sprayground or spray feature is in use. Correct By: 01-Dec-2023
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily. No water temperature records for November 16, 17, 29 or 30.
Take and record the water temperature at least once/day. Correct By: 01-Dec-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 30-November-2023
Comments |
---|
Pool is closed due to no chlorine. Pool chemistry was not tested prior to opening on November 30, 2023. Missing pool chemistry records from November 16, 17, 29 and 30. Re-inspection on December 1, 2023 to re-test pool chemistry. |