[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical

3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
3701-31-04 (C)(8) / Spa water is drained at least every 30 days and is recorded
Spa water was not drained in the last 30 days.
Drain spa immediately and clean before placing the spa back in operation.


Inspection Information


Facility Type: Spa

[?] Inspection Type: Standard

Inspection Date: 10-July-2023


Comments
Free chlorine levels were below required minimum and alkalinity was below required minimum, please adjust pool chemicals accordingly. Supervisor was contacted and spa was closed. Last drainage was not recorded, please write down when spa drainage occurs. Flow gauge was stuck at bottom position, please have it serviced. Reinspection required. KJS Please contact kcooper@wcchd.com or 513-695-1472 when ready for re-inspection.