3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Combined chlorine was not tested daily at pool side prior to use.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
3701-31-04 (B)(4)(a)(v) / Water clarity are not present
no water clarity records kept
Do not operate the pool while the water is unclear. Determine cause of the lack of clarity and immediately correct the issue prior to bathers using the public swimming pool.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation. flow meter stuck
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
3701-31-04 (E)(3)(c) / Location of emergency telephone posted when the phone is not visible.
Sign indicating the location of the emergency device (telephone) was not provided and emergency device was not visible in the pool area. phone calls front desk- must indicate that on the sign
Ensure that a sign informing patrons of the location of the emergency device is always visible in the pool area.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 05-August-2019