[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 02-August-2023


Comments
ORP and flow were below required minimums. Please adjust pool chemistry accordingly or have the chemical controller inspected. Please have the flow gauge serviced.