[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Chlorine disinfectant residual was less than 2 ppm for the spa.
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 2 ppm or above prior to placing the spa back into operation.


Inspection Information


Facility Type: Spa

[?] Inspection Type: Follow-up

Inspection Date: 14-June-2016


The following violation(s) have been corrected since the last inspection.
Comments
Chlorine now at proper level. Thank you.