3701-31-04(D)(6)(a)(4) / Spa free chlorine disinfectant residual shall be above 2 ppm.
Critical Repeat Corrected During Inspection Spa free chlorine disinfectant residual was below 2 ppm.
Do not operate the spa until the chlorine disinfectant residual is at 2 ppm or above. Corrected by 10/11/18 Correct By: 10-Oct-2018
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Repeat Corrected During Inspection Combined chlorine was not tested daily at pool side prior to use.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
Facility Type: Spa
[?] Inspection Type: Follow-up
Inspection Date: 11-October-2018