3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Combined chlorine was not tested daily at pool side prior to use. The readings were only recorded on the paperwork once a day. Ensure the test are conducted every 4 hours the pool is open for use.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use. Correct By: 09-Aug-2021
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained. Observed a huge leak in pump room. Repair before someone gets injured or this leak causes equipment failure.
All equipment must be maintained in accordance with the manufacturers specifications. Correct By: 30-Jul-2021
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities. Correct By: 06-Aug-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 30-July-2021
Comments |
---|
Ensure noted findings are corrected before next routine inspection. Otherwise, all other water parameters met requirements. Ensure that water testing is conducted and recorded every 4 hours you are open. Note: The facility does not have an automatic controller (ACC). |