[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. Flow meter observed reading 95gpm, minimum is 112gpm.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. Correct By: 10-Aug-2023


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 09-August-2023

Comments
Flow meter reading slightly low. All other water quality parameters were within the required ranges at the time of inspection. No problems noted.