3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 04-August-2020
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(1)(c)/Minimum disinfection residual shall be maintained as required. Chlorine disinfectant residual was less than 1 ppm for the pool. Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation. |