3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Chlorine disinfectant residual was less than 1 ppm for the pool.
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
12 ft. non-telescopic reach pole with shepherd's crook was not provided at the unguarded pool. Crook not secured to reach pole.
Provide a 12 ft. non-telescopic reach pole in the pool area at all times.
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 08-August-2017
Comments |
---|
Please have violations brought into compliance for reinspection. |