No critical violations were documented at the time of inspection.
No violations were documented at the time of inspection.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 21-November-2022
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 ( D )(6)(a)/ORP reading shall be 650 millivolts or greater. ORP reading was below 650 mv Have the ACC unit inspected to determined why the ORP is low. |
3701-31-04 (B)(1)(c)/Minimum disinfection residual shall be maintained as required. Chlorine disinfectant residual was less than 1 ppm for the pool Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation. |