3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required flow meter gauge was not functional while the pool is in operation. The flow meter was stuck. Not able to monitor turnover rate. Please repair as soon as possible.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. Correct By: 24-May-2021
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. The pH was 8.0.
Treat the pool water so that the pH is within the acceptable range. Correct By: 24-May-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 18-May-2021
Comments |
---|
Ensure the noted findings are correct before next routine inspection. Otherwise, the pool was in good operating order at time of inspection. Good. |