[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv, observed at 590mv.
Have the ACC unit inspected to determined why the ORP is low. Correct By: 01-Jul-2022
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Flow meter observed stuck at the time of inspection. Unable to get a flow reading.
Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation. Correct By: 01-Jul-2022


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 08-June-2022

Comments
Water chemistry within required parameters. ORP reading low at 590mv. Flow meter observed stuck. Please ensure noted findings are corrected prior to next inspection.