3701-31-04 (B)(5) / Records are maintained for at least two years
The records were not available for review.
Maintain all records and have them available upon request. Correct By: 30-Jun-2018
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8. The pH was 8.0 ppm.
Treat the pool water so that the pH is within the acceptable range. Correct By: 29-Jun-2018
3701-31-04 (D)(7)(e) / Automatic chemical controller shall be on the acceptable list maintained by the director.
Critical The automatic chemical controller was observed not operational. Note: Gave operator a highlighted copy of the regulations for the spa.
Repair or replace the ACC unit with a unit that is on the list.
Correct By: 30-Jun-2018
3701-31-04 (D)(8)(c) / Test kit reagents fresh/ properly stored.
The test kit reagents were observed expired.
Obtain fresh reagents and store them properly. Correct By: 30-Jun-2018
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 31-May-2018
Comments |
---|
Ensure noted violations are corrected before next routine inspection and ensure that pump motor is replaced with original State Plan Approved equipment. Note: If you fail to replace like for like then submit for State approved equipment change. Gave operator equipment change handout. Note: The chlorine is running high and the combined chlorine. |