3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
Repeat SVRS/APSOS/ACC test results/ service records were not maintained.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results.
3701-31-04 (D)(02) / Public swimming pool is continuously disinfected using a chemical feeding device connected to the circulation system
Critical Repeat The pool was not being continuously disinfected using a chemical feeding device connected to the circulation system. ACC is non-functioning; error message and alarm on the unit.
Repair or replace the disinfection system so that the pool is continuously being disinfected.
3701-31-04 (D)(7)(a) / pH and ORP values for chlorine/bromine shall be continuously monitored.
Critical Repeat pH values were not continuously monitored.
Have the ACC unit serviced so that the pH values are continuously monitored
3701-31-04 (D)(7)(b) / pH and ORP values shall be displayed.
Critical Repeat ORP value was not displayed on the ACC unit.
Have the ACC unit serviced or replaced so that the ORP value is displayed
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 30-October-2023
Comments |
---|
Pool chemistry levels are within range, good job! ACC is non-functioning and is flashing an error message, ORP could not be displayed. |