No critical violations were documented at the time of inspection.
No violations were documented at the time of inspection.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 10-July-2014
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 ( D )(6)(a)/ORP reading is above 650 mv ORP reading was 645 mv Have the ACC unit inspected to determined why the ORP is low. |
3701-31-04 (C)(2)/pH is within 7.2 to 7.8 pH was 8.0. Treat the pool water so that the pH is within the acceptable range. |
3701-31-04 (D)(6)(a)/Pool free chlorine disinfectant residual is above 1 ppm. Pool free chlorine disinfectant residual was 0 ppm. Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. |
Comments |
---|
No problems noted at the time of the inspection. Chemicals within parameters. |