3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. ORP was observed at 540mv
Have the ACC unit inspected to determined why the ORP is low. Correct By: 01-Jul-2022
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Chlorine was tested and resulted with 0.8 of total chlorine and 0.6 of free and 0.2 of combined. Free chlorine should be a minimum of 1.0ppm.
Ensure disinfectant residuals meet the minimum requirements. Correct By: 01-Jul-2022
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Flow meter observed to be stuck. Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation. Correct By: 01-Jul-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 15-June-2022
Comments |
---|
Chlorine level was low. ORP reading was low. Flow meter observed to be stuck. Other water chemistry within required parameters. Called Jeff on the 15th about chlorine levels, left a voice mail. Please ensure all noted findings are corrected prior to next inspection. |