No critical violations were documented at the time of inspection.
No violations were documented at the time of inspection.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 14-March-2014
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(1)(g)/Water clarity is sufficient to see the pool bottom (or Secchi disc) Water clarity was not sufficient to see the pool bottom (or Secchi disc) Do not operate the pool when water clarity is poor. Pool was voluntarily closed until remediated. Correct By: 14-Mar-2014 |
3701-31-04 (B)(4)/The licensee /authorized representative is keeping records The licensee /authorized representative was not keeping or maintaining operational records. No records were being recorded. All facility records must be maintained and available for review upon request. |
3701-31-04 (B)(4)(a)(i)/Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features Disinfection residuals were not tested daily at pool side and/or at the required intervals for pools/automatic chemical controllers/special features. Water had not been tested prior to opening. Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. If an ACC is in use the disinfectant residual must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the disinfectant residual must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use. |
3701-31-04 (C)(2)/pH is within 7.2 to 7.8 pH was outside the range of 7.2 to 7.8. pH was over 8.0. Treat the pool water so that the pH is within the acceptable range. |
Comments |
---|
All of the violations from previous inspection have been corrected. A weekly pool records form was provided during inspection. Please continue to record readings 2 times per day. Thank you. |