3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. Correct By: 15-Aug-2023
3701-31-04 (D)(02) / Public swimming pool is continuously disinfected using a chemical feeding device connected to the circulation system
Critical Repeat The pool was not being continuously disinfected using a chemical feeding device connected to the circulation system
Repair or replace the disinfection system so that the pool is continuously being disinfected. Correct By: 15-Aug-2023
3701-31-04 (D)(8)(c) / Test kit reagents fresh/ properly stored.
Repeat Test kit reagents were not fresh or stored properly. All reagents in pool kit were beyond expired.
Obtain fresh reagents and store them properly. Correct By: 15-Aug-2023
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Repeat Pool free chlorine disinfectant residual was below 1 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. Correct By: 05-Sep-2023
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 15-August-2023
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(6)(h)/Required meters and gauges maintained/functional Required meters and gauges were not maintained or were not functional while the pool is in operation. Flow meter was broken at time of inspection. Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation. Correct By: 15-Aug-2023 |
3701-31-04 (C)(2)/pH is within 7.2 to 7.8 pH was outside the range of 7.2 to 7.8. Treat the pool water so that the pH is within the acceptable range. Correct By: 15-Aug-2023 |
3701-31-04 (C)(3)/Total alkalinity is at or greater than 60 ppm Total alkalinity was less than 60 ppm. Raise the total alkalinity to at least 60 ppm. Correct By: 15-Aug-2023 |
3701-31-04(D)(6)(a)(1)/Combined chlorine shall not exceed 1.0 ppm. Combined chlorine was greater than 1.0 ppm. Treat the pool so that the combined chlorine is less than 1 ppm. Correct By: 15-Aug-2023 |
Comments |
---|
Follow up for chlorine levels and technician from ecolab to inspect automatic chemical control feeder. Possibility of removing automatic chemical control feeder. |