3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (D)(7) / Public spa shall have a functional automatic chemical controller
Critical Repeat ACC is not properly operating, stuck on error message.
Fix ACC to good working condition and proper function. Correct By: 09-Apr-2024
3701-31-04 (D)(7)(b) / pH and ORP values shall be displayed.
Critical Repeat ORP value was not displayed on the ACC unit.
Have the ACC unit serviced or replaced so that the ORP value is displayed. Correct By: 09-Apr-2024
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Repeat Pool free chlorine disinfectant residual was below 1 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 18-April-2024
Comments |
---|
Warning Placard was posted for no presence of chlorine, automatic chemical control feeder not operating, and no pool flow. |