3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
3701-31-04 (D)(02) / Public swimming pool is continuously disinfected using a chemical feeding device connected to the circulation system
Critical Repeat The pool was not being continuously disinfected using a chemical feeding device connected to the circulation system
Repair or replace the disinfection system so that the pool is continuously being disinfected.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 27-July-2023
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04(D)(6)(a)(2)/Pool free chlorine disinfectant residual shall be above 1 ppm. Pool free chlorine disinfectant residual was below 1 ppm. Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. |
Comments |
---|
Free chlorine corrected by operator at time of inspection. Combined chorine, pH, and Alkalinity were outside of required ranges. Please adjust pool chemistry accordingly. KJS |