3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was 10 ppm.
Raise the total alkalinity to at least 60 ppm.
3701-31-04 (D)(7)(b) / pH and ORP values shall be displayed.
Critical Repeat An error on the ACC unit was preventing the ORP from being read. Correct the error so that the ORP values can be displayed and the ACC unit functions properly.
Have the ACC unit serviced or replaced so that the ORP value is displayed
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical The pool was entirely devoid of chlorine. The pool was closed, and will remain closed until the chlorine residual can be brought up to 1 ppm or higher.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 31-January-2022
Comments |
---|
Facility has not done anything to correct the error on the ACC unit. Without the ACC unit functioning properly, the facility will need to test water quality every 4 hours during operation until the ACC is unit is repaired or replaced. Measurements will need to being at 10 am every day before the pool is opened to guests. |