3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. Observed at 612mV.
Have the ACC unit inspected to determined why the ORP is low. Correct By: 21-Jun-2023
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. Observed pH to be 8.0
Treat the pool water so that the pH is within the acceptable range. Correct By: 21-Jun-2023
3701-31-04 (D)(7)(c) / Audible/visual alarm shall activate when unit is malfunctioning or when pH or ORP levels are not acceptable.
Critical The ACC unit was not activating an audible or visual alarm when unit malfunctioned or when pH or ORP levels were not acceptable. ACC was alarming for no flow at time of inspection.
Have the ACC unit serviced or replaced so that the audible or visual alarm is activated when necessary. Ensure that proper flow rates are present. Correct By: 21-Jun-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 20-June-2023
Comments |
---|
"No flow" alarm going off upon inspection. Low ORP observed, slightly high pH also observed. Other parameters were within required ranges. Please ensure pumps and ACC are functioning properly prior to operating pool. |