3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
Repeat An automatic controller and pH/chlorine feeder have been added without prior approval.
Submit change of equipment form to Ohio Department of Health for approval. Correct By: 30-Apr-2018
3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Repeat The PIC had to manually add chemicals to pool because the Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection.
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation. Correct By: 30-Mar-2018
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat The ladder to pool was very loose.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair. Correct By: 30-Apr-2018
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 30-March-2018
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 ( D )(6)(a)/ORP reading shall be 650 millivolts or greater. ORP reading was below 650 mv. The ORP was 565. Have the ACC unit inspected to determined why the ORP is low. Correct By: 30-Apr-2018 |
3701-31-04 (B)(1)(c)/Minimum disinfection residual shall be maintained as required. The chlorine reading was 0 ppm and the combined chlorine was .4 ppm. NOTE: Recommend superchlorinating and determine salt level to ensure the salt is properly converting salt to sodium chloride. Ensure chlorine generator is operating properly. Minimum disinfection residual shall be maintained as required. Correct By: 29-Mar-2018 |
3701-31-04 (B)(1)(g)/Water clarity shall be sufficient to see the pool bottom (or Secchi disc). Water clarity was not sufficient to see the pool bottom main drain, entry steps, or ladder entry steps. Do not operate the pool when water clarity is poor. Note: Recommend closing pool until clarity returns and you’re able to see main drain and steps. This is a customer safety issue. Correct By: 30-Mar-2018 |
Comments |
---|
The quick response for corrective actions was much appreciated. Good job! Ensure the other noted violations are corrected before next routine inspection. |