3701-31-04(D)(6)(a)(1) / Combined chlorine shall not exceed 1.0 ppm.
Combined chlorine was greater than 1.0 ppm. Combined Chlorine is 2.0 ppm
Treat the pool so that the combined chlorine is less than 1 ppm.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Corrected During Inspection Pool free chlorine disinfectant residual was below 1 ppm. Free chlorine was .2 ppm. Corrected chlorine was raised to 3.0 during the inspection.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 25-July-2016
Comments |
---|
Please replace 2 nd salt cell to ensure that chlorine level is being maintained. |