3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Repeat Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 26-April-2022
Comments |
---|
Thank you for correcting previous violations. |