3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for all water pumps.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 30-July-2021
Comments |
---|
Facility clean at the time of inspection. All required equipment present and in good repair at the time of inspection. Flow Meter not working. |