3701-31-04 (B)(1)(d) / Circulation/Disinfection system shall operate properly.
Critical Corrected During Inspection The pump was not on, no water was circulating. When the circulation system is brought back on, the pool may be opened.
The pool was closed until the pump could be switched on again.
3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Repeat Disinfection residuals were not tested daily at pool side and/or at the required intervals for pools/automatic chemical controllers/special features. No records maintained.
Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. If an ACC is in use the disinfectant residual must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the disinfectant residual must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Repeat Combined chlorine was not tested daily at pool side prior to use. No records maintained.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(4)(a)(iii) / pH is tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Repeat pH was not tested daily at pool side and/or at required intervals for pools/automatic chemical controllers/special features. No records maintained.
pH must be tested prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use pH must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the pH must be tested at 1 special feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Repeat Water temperatures were not being recorded daily. No records maintained.
Take and record the water temperature at least once/day.
3701-31-04 (B)(4)(a)(v) / Water clarity are not present
Water clarity was not sufficient to see the pool bottom (or Secchi disc). No records maintained.
Do not operate the pool while the water is unclear. Determine cause of the lack of clarity and immediately correct the issue prior to bathers using the public swimming pool.
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly. No records maintained.
Test total alkalinity at least once/week.
3701-31-04 (D)(7)(b) / pH and ORP values shall be displayed.
Critical Repeat The ORP was not displayed due to the circulation system being turned off.
Have the ACC unit serviced or replaced so that the ORP value is displayed
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 25-May-2022
Comments |
---|
Pool was closed until the circulation system can be turned on again. No records were being taken. Administrative hearing may be required. |