3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. Automatic chemical control panel appears to be malfunctioning.
All equipment must be maintained in accordance with the manufacturers specifications.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation. Flow meter appears stuck.
Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 12-July-2023
Comments |
---|
The spa, although its heating element is broken, must maintain a 30 minute turnover rate and the water must be completely drained every 30 days due to how it is permitted. |