3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
Repeat SVRS/APSOS/ACC test results/ service records were not maintained.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results.
3701-31-04 (D)(02) / Public swimming pool is continuously disinfected using a chemical feeding device connected to the circulation system
Critical The pool was not being continuously disinfected using a chemical feeding device connected to the circulation system. ACC is non-functioning and displays an alarm.
Repair or replace the disinfection system so that the pool is continuously being disinfected.
3701-31-04 (D)(7)(a) / pH and ORP values for chlorine/bromine shall be continuously monitored.
Critical pH values were not continuously monitored.
Have the ACC unit serviced so that the pH values are continuously monitored
3701-31-04 (D)(7)(b) / pH and ORP values shall be displayed.
Critical Repeat ORP value was not displayed on the ACC unit.
Have the ACC unit serviced or replaced so that the ORP value is displayed
3701-31-04 (E)(2)(d) / First aid kit provided
Repeat First aid equipment was not provided. No gloves or gauze for the first aid kit.
Provide first aid equipment, including a first aid kit, at the pool at all times. Please provide gloves and gauze for the first aid kit.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 18-September-2023
Comments |
---|
Pool chemistry levels are within range, good job! ACC is non-functioning and is flashing an error message, ORP and pH could not be displayed. |