3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Corrected During Inspection Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
3701-31-04 (E)(2)(b)(i) / 12 ft. non-telescopic reach pole with Sheppard's crook & a USCG Type IV personal flotation device with 30 - 60 foot throw line.
12 ft. non-telescopic reach pole with Shepherd's crook and/or a USCG Type IV personal flotation device with 30 - 60 foot throw line was not provided at the guarded pool. Floatation device missing.
Provide the non-telescopic reach pole and personal floatation device at the pool at all times.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 28-July-2017
Comments |
---|
Chemicals were corrected during inspection. |