3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. Flow is too low.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 12-January-2015
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (D)(6)(a)/Pool free chlorine disinfectant residual is above 1 ppm. Pool free chlorine disinfectant residual was below 1 ppm. Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. |
Comments |
---|
Chlorine level has been adjusted to within range. Please have flow, pH and alkalinity adjusted to proper ranges prior to reinspection. |