3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Corrected During Inspection Chlorine disinfectant residual was less than 1 ppm for the pool. Staff was onsite and raised levels.
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Combined chlorine was not tested daily at pool side prior to use.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 27-June-2017
Comments |
---|
Please ensure the above has been corrected prior to next standard inspection. |