[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. The ORP was 200, the alarm was blinking.
Have the ACC unit inspected to determined why the ORP is low. Correct By: 05-Jul-2021
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Repeat No emergency device (telephone) was on site. The PIC stated, "a telephone will be added to pool side area as soon as possible."
Ensure that the emergency device is functioning properly and rings to the emergency response authorities. Correct By: 05-Jul-2021


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 29-June-2021