3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat The pH was 7.0.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was 40 ppm.
Raise the total alkalinity to at least 60 ppm.
3701-31-04 (D)(7)(b) / pH and ORP values shall be displayed.
Critical Repeat An error with the ACC was hiding the ORP value, making it unreadable. Correct the error or replace the ACC so that the ORP may be displayed. This violation has persisted for several months.
Have the ACC unit serviced or replaced so that the ORP value is displayed
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 30-December-2021