3717-1-05(H) / Capacity.
Critical Repeat Observed the water source and system is not of sufficient capacity at the time of inspection to meet the peak hot water demands based on FDA guidance.
To ensure proper cleaning and sanitation, the water source and system, hot water generation, and distribution systems shall be of sufficient capacity to meet the peak water and hot water demands of the RFE.
3717-1-05.3(I) / Other liquid wastes and rainwater.
Repeat Observed improper draining of condensation from walk-in refrigeration units and air conditioner at the time of inspection.
Condensate drainage and other nonsewage liquids and rainwater shall be drained from point of discharge to disposal according to law. Ensure condensate drain lines for refrigeration equipment is air-gapped at least 2" to protect against backflow contamination.
3717-1-06.4(A) / Repairing.
Observed the door and door seals for the walk-in cooler were in need of repair at the time of inspection.
The physical facilities shall be maintained in good repair. Repair/replace the damaged door and seals for the walk-in cooler.
Facility Type: Commercial RFE < 25000 sq. ft.
[?] Inspection Type: Other
Inspection Date: 11-December-2014
Comments |
---|
Inspection conducted to verify walk-in cooler is maintaining TCS foods at a temperature that is 41 degrees Fahrenheit or lower. Observed multiple food items stored within the walk-in cooler were being maintained at acceptable temperatures at the time of inspection. Provided a set of example temperature logs which may be used to monitor and record temperatures for equipment. |