[?] A summary of the violations found during the inspection are listed below.

No critical violations were documented at the time of inspection.

No violations were documented at the time of inspection.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Follow-up

Inspection Date: 22-March-2017


The following violation(s) have been corrected since the last inspection.
3701-31-04 (B)(1)(c)/Minimum disinfection residual shall be maintained as required.
Chlorine disinfectant residual was less than 1 ppm for the pool.
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
Comments
Water chemistry within required parameters, no problems at time of inspection.