[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for all water pumps. Flow meter is too close to coupling.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 06-June-2014


Comments
Chemicals are within parameters.