3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Repeat Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection. new controller has not been installed yet.
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation.
3701-31-04 (B)(1)(g) / Water clarity shall be sufficient to see the pool bottom (or Secchi disc).
Critical Repeat Water clarity was not sufficient to see the pool bottom (or Secchi disc). Observed very cloudy water and could not see pool bottom. Pool was closed upon inspection and will not reopen until problem is fixed.
Do not operate the pool when water clarity is poor. Correct By: 28-Mar-2018
3701-31-04(D)(6)(a)(1) / Combined chlorine shall not exceed 1.0 ppm.
Repeat Combined chlorine was greater than 1.0 ppm. Observed combined chlorine at 1.2 ppm
Treat the pool so that the combined chlorine is less than 1 ppm.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 28-March-2018
Comments |
---|
spoke with owner. Pool is to remained closed until water clarity improves. |