3701-31-04 (B)(1)(c) / Minimum disinfection residual provided as required
Critical Chlorine residual under 1.0 ppm.
Chlroine residual shall be at least 1.0 ppm for effective disinfection.
3701-31-04 ( D )(6)(a) / ORP reading is above 650 mv
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records. Readings on weekends are not being recorded.
All facility records must be maintained and available for review upon request.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation. Flow meter stuck during inspection.
Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 22-July-2014
Comments |
---|
A reinspection will be conducted to ensure the above have been corrected. |