[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. Contoller is alarming as no flow. Please repair or replace controller
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. pH is 7.0
Treat the pool water so that the pH is within the acceptable range.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 16-May-2017


Comments
Raise pH. Chemical controller is alarming no flow, but there was flow through both the system and the controller at the time of the inspection. Please repair/replace controller.