[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
Repeat 12 ft. non-telescopic reach pole with shepherd's crook was not provided at the unguarded pool. Shepherd's crook and reach pole in pump room, should be available for use if needed.
Provide a 12 ft. non-telescopic reach pole in the pool area at all times.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Follow-up

Inspection Date: 11-June-2019


The following violation(s) have been corrected since the last inspection.
3701-31-04 (C)(2)/pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (C)(3)/Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
Comments
Water chemistry within required parameters. Please have remaining violation brought into compliance by next routine inspection.