[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(iii) / pH is tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
pH was not tested daily at pool side and/or at required intervals for pools/automatic chemical controllers/special features. Readings only being recorded once per day. Pool is open from 7am to 11 pm. Two readings must be taken and recorded.
pH must be tested prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use pH must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the pH must be tested at 1 special feature every 6 hours the sprayground or spray feature is in use.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 12-November-2015


Comments
Please have the above corrected prior to next inspection.