[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.


Inspection Information


Facility Type: Spa

[?] Inspection Type: Follow-up

Inspection Date: 19-September-2016


The following violation(s) have been corrected since the last inspection.
3701-31-04 (B)(1)(c)/Minimum disinfection residual shall be maintained as required.
Chlorine disinfectant residual was less than 2 ppm for the spa
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 2 ppm or above prior to placing the spa back into operation.