3701-31-04 (B)(1)(d) / Circulation/Disinfection system is operating properly
Critical Corrected During Inspection Chlorine level at 0 ppm.
Chlorine must be at least 1.0 ppm. Company was called and chlorine levels were brought up to 3.0 ppm.
3701-31-04 ( D )(6)(a) / ORP reading is above 650 mv
Corrected During Inspection ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. ORP raised to 875.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation. Flow meter is stuck.
Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 29-July-2014
Comments |
---|
Pool company was called to correct chlorine issue. Chlorine was raised to 3. 0 ppm and ORP to 875. |