[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(g) / Water clarity is sufficient to see the pool bottom (or Secchi disc)
Critical Water clarity was not sufficient to see the pool bottom (or Secchi disc)
Do not operate the pool when water clarity is poor. Pool was voluntarily closed until remediated. Correct By: 14-Mar-2014

3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Repeat The licensee /authorized representative was not keeping or maintaining operational records. No records were being recorded.
All facility records must be maintained and available for review upon request.
3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Disinfection residuals were not tested daily at pool side and/or at the required intervals for pools/automatic chemical controllers/special features. Water had not been tested prior to opening.
Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. If an ACC is in use the disinfectant residual must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the disinfectant residual must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. pH was over 8.0.
Treat the pool water so that the pH is within the acceptable range.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 13-March-2014


Comments
A reinspection will be conducted to ensure the above have been corrected. A copy of the weekly records sheet has also been sent to operator. Please ensure that pH pumps are kept on at all times so that the automatic controller can properly function.