[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. The ORP was 570.
Have the ACC unit inspected to determined why the ORP is low. Correct By: 05-Jul-2021
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. The pH was 8.0.
Treat the pool water so that the pH is within the acceptable range. Correct By: 05-Jul-2021


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 28-June-2021


Comments
Ensure the noted finding is correct before next routine inspection. Otherwise, all the other water parameters met requirements and paperwork was being filled out correctly. Good job!