3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Corrected During Inspection Pool free chlorine disinfectant residual was below 1 ppm. The free chlorine was .6 ppm. The pool operator was notified and asked the front desk to place a pool closed sign up while he was in a staff meeting. Once he makes proper adjustments he will re-open pool.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. Correct By: 27-Mar-2023
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv. The ORP reading was590 mv. The PIC was notified and will make proper adjustment.
Have the ACC unit inspected to determined why the ORP is low. Correct By: 28-Feb-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 27-February-2023
Comments |
---|
Ensure noted findings are corrected before next routine inspection. Otherwise, all other water parameters were within requirements and reports were readily available at time of inspection. Good job! |