3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical No chlorine residual in pool. Must be at least 1.0 ppm.
3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Repeat The licensee /authorized representative was not keeping or maintaining operational records.
All facility records must be maintained and available for review upon request.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 20-August-2015
Comments |
---|
Chlorine must be raised to proper levels. |