3701-31-04 (D)(7)(e) / Automatic chemical controller shall be on the acceptable list maintained by the director.
Critical Repeat Automatic chemical controller was still not operating properly.
Repair or replace the ACC unit with a unit that is on the list.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required flow meter gauge was not functional while the pool is in operation. The flow meter was stuck.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. Correct By: 31-Mar-2019
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Cyanuric acid level exceeded 70 ppm. The cyanuric acid was 100 ppm.
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly. Correct By: 28-Feb-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 30-January-2019
Comments |
---|
Ensure noted violations are corrected before next routine inspection. Otherwise, all other water parameters were in good working order at time of inspection. Note: The new general manager will be on site soon and details regarding the ACC will be addressed. |